Woodward Electronic Control Systems
Electronic Controls for Steam Turbines
Peak 150® Steam Turbine Control
Woodward’s Peak®150 steam turbine control is a low-cost, compact, digital control for single-valve or single-valve rack steam turbines. It provides convenient operator control and speed display from the front panel. It is housed in a watertight and dust tight enclosure. A corrosion-resistant enclosure designed to meet NEMA 4X requirements is also available.
The Peak 150 digital control is designed to control a steam turbine driving a mechanical load. It provides tight control of speed (NEMA D) and includes an input for a 4-20 mA remote speed control signal, which can be used for a process-generated input to control the speed setting.
Other features include dual speed control dynamics and overspeed trip test capabilities.
Learn more from the Peak 150 product specification
Inputs
Magnetic Pickup Inputs (2):
- Two identical inputs, high-signal-selected
- Minimum input voltage 1 Vrms, minimum frequency 200 Hz, maximum frequency 15 kHz
Analog Input (1):
- Remote Speed Setting signal (4–20 mA or 1–5 Vdc, internal jumper selectable)
Discrete Inputs (8)
- Remote (isolated, 5–28 Vdc)
Options:
- Raise speed
- Lower speed
- Emergency stop
- Alarm reset
- Remote speed set enable
- Start
- Idle/minimum governor
- Select high dynamics or overspeed test
Outputs
Analog Outputs (2):
- Actual speed output (scalable, 4–20/0–1 mA)
- Configurable readout (scalable, 4–20/0–1 mA)
Options:
- Actual speed
- Speed setpoint
- Actuator output
- Remote speed setpoint
- Valve ramp value
Actuator Output (1)
- 4–20 or 0–200 mA (internal jumper selectable)
Relay Outputs (4)
- Internal jumpers provide choice of normally-open or normally-closed contacts
Operator Control Panel
Keypad Switches (6) Options
- Raise speed
- Lower speed
- Emergency trip
- Start
- Overspeed test
- Alarm reset
LED Indicators (6)
- Remote speed setting signal status
- Shutdown status
- MPU #1 status
- MPU #2 status
- CPU status
- Overspeed test status
Power Input
- Models are available with these input power requirements:
- 24 Vdc
- 90–150 Vdc or 88–132 Vac, 47–63 Hz
Maximum power consumption, all models: 38 W
Operating Ambient Temperature
- –25 to +65 °C (–13 to +149 °F)
Storage Ambient Temperature
- –40 to +85 °C (–40 to +185 °F)
Humidity
- Designed to meet US MIL-STD-810D, Method 507.2, Procedure II, induced, non-hazardous, cycle 5 (fifteen 24-hour cycles, varying 19–75% humidity, over 33–63 °C)
Vibration
Shock
- US MIL-STD-810C, Method 516.2, Procedure 1
North American Regulatory Compliance
- UL and cUL listed for Class I, Division 2, Groups A, B, C, & D
Dimensions
- Width 483 mm (19 inches)
- Height 310 mm (12.2 inches)
- Depth 105 mm (4.1 inches)