MCDTV4

     

    HighPROTEC Transformer Differential Protection

    HighPROTEC Transformer Differential Protection


    The MCDTV4 offers an all-in-one solution for HV, MV and LV transformers and it offers much more than just a differential protection package. Furthermore it can detect critical operation states based on voltage measurement (e.g. Overexcitation). The MCDTV4 provides in addition to that an Interconnection package. This can be used for mains protection at the point of  common coupling (e.g. for directional reactive power undervoltage protection). The integrated backup protection package enables the MCDTV4 to act as backup protection (e.g. for downstream breakers). Additional features like demand management are available without extra charge. 

     
    Device MCDTV4
    Line HighPROTEC
    Binary inputs 10(+8)
    Analog Inputs Optional
    Analog Outputs Optional
    Control and detection of switchgears Yes
    Control and supervision of a circuit breaker (remote or local) 6
    Current transformer inputs 8
    Output relays 7
    Voltage transformer inputs 4
    Watchdog relay 1
    Circuit breaker failure protection [50BF] Yes
    Current transformer supervision [60FL] Yes
    Differential protection: Transformer [87T] Yes
    Directional time overcurrent protection [67] Yes
    Earth fault directional feature [67N] Yes
    Earth fault protection [50N/51N] Yes
    Fault Ride Through (FRT) Yes
    Frequency gradient [81] Yes
    Frequency protection [81O/U] Yes
    IEC 60870-5-103 Optional
    Inrush stabilisation (2nd harmonic) Yes
    IRIG-B00X Yes
    Manual Yes
    Modbus (TCP) Optional
    Modbus RTU Protocol Optional
    Negative sequence protection [46] Yes
    Output relay matrix Yes
    Parameter sets 4
    Phase balance [47] Yes
    Power direction [32/37] Yes
    Profibus DP Optional
    Programmable Logic Yes
    Q->&V< Yes
    Reset / Blocking Yes
    Residual voltage [59N] Yes
    Resistance earthed / solidly earthed [50N/51N] Yes
    Synchrocheck [25] Optional
    Time Synchronization via SNTP Yes
    Sensitive EF isolated/compensated [50SN/51SN] Yes
    Thermal replica [49] Yes
    Time Date Yes
    Time overcurrent protection [50/51] Yes
    Trip- and auxiliary relays [86] Yes
    Trip circuit resp. control circuit supervision [74TC] Yes
    Vector surge / mains decoupling [78] Yes
    Voltage protection [27/59] Yes
    Voltage transformer supervision [60FL] Yes
    IEC 61850 Optional
    Intertripping Yes
    Time Synchronization via Modbus Yes
    Time Synchronization via IEC 60870-5-103 Optional
    Voltage Restraint Overcurrent [51V] Yes
    Voltage Restraint Controlled [51C] Yes
    Demand Management Yes
    THD (Todal Harmonic Distortion) Protection Yes
    RTD Temperature Protection [23] Optional
    Disturbance recorder Yes
    Event recorder Yes
    Fault recorder (none volatile) Yes
    Trend recorder Yes
    ANSI: IEC:
    24; U/f, (dU/df)
    29; U<
    32; S<,S<<,S>,S>>
    32F/R; Pf>, Pr>
    37; I<t
    46; I2>
    47; U2>
    49; -
    50; I>,I>>
    50BF; CBF
    50H; I>H2
    50N; IE>,IE>>
    50Ns/51Ns; INsensitiv>
    50S; I>,I>> sensitiv
    51N; -
    51V; I>f(U)
    55; PF
    59; U>
    59N; UE>
    60FL; -
    64REF; IE>t restr.
    67; I> ->, I>> ->
    67N; IE> ->
    74TC; -
    78; ΔΘ
    79; AR/AWE
    81; f<, f>
    81 U/O; f<, f>
    81R; ROCOF
    86; -
    87T; -

     

    All shown details without any guarantees!  We reserve the right of changes without prior notice.