UMT 1 Series

Woodward Measuring Transducers with RMS Sensing

  device_umt_1.jpg
Woodward’s UMT 1 Series consists of measuring transducers that feature true RMS sensing. Measured values are calculated and displayed on a two-line, 16-character LC Display. They can either be assigned to analog outputs (configurable as -20 to 20 mA, 0 to 20 mA, or 4 to 20 mA) or transmitted to a higher-level control system via RS-485 or Profibus DP interface.

The primary measured values of voltage and current are used to calculate the values for active, re-active, apparent power, power factor (cosphi), kWh and kvarh. An impulse output is also provided to output kWh or kVarh values.

Features include:

  • True RMS sensing
  • Class 0.5 accuracy
  • RS-485 Modbus RTU Slave or Profibus DP communication
  • Configurable measuring system for either single-phase, three-phase, or a combination of both
  • Front panel configurable
 

Packages

The UMT 1 Series is available with different feature packages. The following table shows the differences between these packages. 

 

UMT 1 Series

Model 

UMT 1 

UMT 1 

UMT 1 

UMT 1 

Package

A3

A3SU

A3SU

A6

Analog outputs

3

3

3

6

RS-485 (Modbus)

---

---

---

Profibus DP

---

---

---


 

Specifications

Power supply 

24Vdc (8 to 30 Vdc)

Consumption

max. 10W

Ambient temperature (operation)

-20 to 70 °C / -4 to 158 °F

Ambient humidity

95 %, non-condensing

Voltage AC input 

115Vac or 400Vac true RMS

Accuracy

Class 0.5

Current AC input 

1A or 5A true RMS

Accuracy Iac

Class 0.5

Analog outputs (isolated)

-20/0/4 to 20 mA

Housing 

 

Front panel mounting

Plastic housing

Dimension (WxHxD)

96 × 72 × 130 mm

Sealing (front/back)

IP42/IP21

Weight 

Approx. 800 g

 


 

Applications

application_umt_1.gif

Approvals

CE.gif  UL.gifcUL.gif
 


 