GCP-30

Woodward’s Genset Control For Multiple/Parallel Operation Provides Reliability

 device_gcp-30.jpg 

Woodward’s GCP-30 Series genset controllers are designed to provide total control for multiple, medium- to large-sized applications. A network of the compact, versatile GCP-30 controls is capable of controlling up to 14 gensets with automatic sequencing. Load management features include automatic base loading/peak shaving, import/export control, and emergency power/back up power generation. The GCP-30 Series is well known in the market for highly reliable soft- and hardware.

Features include: 

  • True RMS voltage and current sensing for Generator, Bus, and Mains
  • Complete engine/generator protection, plus mains monitoring
  • Relay manager for programming relay outputs according to selectable discrete and analog conditions
  • Load share 14 gensets in island mode or paralleled to the utility
  • Different load or process dependent start/stop sequencing modes with active and reactive power load sharing
  • Communication to engine ECU’s (CAT, MDEC, J1939 based protocols), PLC’s, external I/O extension cards
  • Connection to Woodward LS4 to run multiple breaker applications
  • Configurable discrete Inputs and Relay Outputs
 

Packages

 

GCP-30 Series

Model 

GCP-31 

GCP-32 

Package

BPQ

XPD

XPQ

XPQS

 +B03

XPQ

 +SC10

BPQ

XPD

XPQ

XPQ

 +SB03

XPQ

 +SC10

GCB control/MCB control

●/-

●/-

●/-

●/-

●/-

●/-

●/-

●/-

●/-

●/-

External CB control

---

---

---

---

---

Real-time clock

---

---

Event recorder

---

---

External mains power measurement (0 to 20 mA)

---

---

Active power setpoint
(0/4 to 20 mA)

---

---

Analog inputs/outputs

---

7/2

7/2

7/2

7/2

---

7/2

7/2

7/2

7/2

External operation model selection (DI)

---

---

Analog/PWM controller for speed/kW and V/var control

---

---

CAN bus interfaces

1

1

1

1

2

1

1

1

1

2

RS-232 interfaces

---

---

---

1

---

---

---

---

1

---

Caterpillar CCM protocol

---

---

---

---

---

---

---

---

J1939 protocol

---

---

---

---

---

---

---

---


 

Specifications

Power supply 

12/24Vdc (9.5 to 32 Vdc)

Consumption

max. 20W

Ambient temperature (storage)

-30 to 80 °C

Ambient temperature (operation)

-20 to 70 °C

Ambient humidity

95 %, non-condensing

Voltage AC input 

120Vac and 480Vac true RMS

Accuracy

Class 1

Current AC input 

1A or 5A true RMS, isolated

Accuracy Iac

Class 1

Discrete inputs (isolated)

Range: 12/24Vdc (6 to 32Vdc)

Relay outputs 

Relays, dry contacts

Load (resistive)

2A@24Vdc and 250Vac

Analog inputs 

0/4 to 20mA

Analog outputs (isolated)

0/4 to 20 mA (freely scalable)

Housing 

 

Front panel mounting

Plastic housing

Dimension (WxHxD)

144 × 144 × 118 mm

Sealing (front/back)

IP42/IP21

Weight 

Approx. 1,850 g (depending on model)


 

Applications

application_gcp-30.gif

 

Approvals

CE.gif UL.gif cUL.gif GOST-R.gif 


 


 