(ASG 411)
The
SPM-D11 is a microprocessor-based synchronizer designed for use on one or
three-phase AC generators equipped with Woodward or other compatible speed
controls and automatic voltage regulators. The SPM-D11 synchronizer provides
automatic frequency, phase and voltage matching using either analog- or discrete
output bias signals.
It combines synchronizing for one circuit breaker, load and power factor control
or isochronous load sharing and generator protection.
- Phase match or slip frequency synchronization with voltage matching
- 2-phase sensing of generator and busbar
- Synchronization time monitoring
- Load/var sharing
- Real power control
- True RMS power calculation
- Generator real power set point by parameter or via 0/4 to 20 mA
- Soft unloading
- Power factor control
- Power factor set point by parameter
- Power limit value with relay output
- Discrete raise/lower for speed/load
- Discrete raise/lower for voltage/power factor
- Two-line Liquid Crystal display
- Operation and alarm indication
- Control activity and breaker state indication
- Synchroscope
- Generator/busbar value display
- English/German display language
- PC and front panel configurable
- Generator over/undervoltage (ANSI# 59/27)
- Generator over/underfrequency (ANSI# 81O/U)
- Generator overload (ANSI# 32)
- Generator reverse/reduced power (ANSI# 32R/F)
Models: SPM-D11/LSXR
- Analog bias outputs for voltage and speed freely configurable
- Speed bias output configurable as 500 Hz PWM output and adjustable voltage level
- Two raise/lower outputs configurable for either speed or voltage
All units are available with 12/24 Vdc DIs or wide-range DIs (18 to 250 Vac/dc).
Please refer to the Product Specs for detailed information.
Certifications / registrations: UL/cUL, CE
Download Product Specs:
Download Product Manuals:
Download LeoPC1 Configuration Files:
Download LeoPC1 Configuration Program
Please refer to the
Woodward Worldwide Directory and contact your
local sales office for questions about pricing and delivery or product support.
Return to top of the page
Note: Information contained herein is intended for and appropriate to
the purposes of this publication. Woodward reserves the right to update or otherwise
revise any portion of this publication at any time. Technical data and detailed
information is available in Woodward product specs. Specific reliance should be given
only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate
for the specific facts, circumstances and applications.
|