The streamlined features of the easYgen-1000 turns this engine-generator control system into the ideal
solution for your single unit application. With the flexible breaker control logic you can easily configure
the easYgen-1000 for one of four operating modes - from a simple measuring transducer and engine control up to
a full two-breaker, open-transition operation device. The simple automatic start/stop logic and automatic load
transfer capabilities round out the features of the easYgen-1000 to cover all stand-by and emergency applications.
Features:
- FlexAppTM Technology
- Operation mode:
Auto, Manual, Test (load & no load)
- Breaker configuration:
GCB and MCB
- Breaker control:
Open-close control, only open control, breaker monitoring
- Load transfer by open transition
- Start/stop logic for Diesel/gas engines
- LogicsManager to adapt programmable relays to your requirements
- Complete engine, generator, and mains protection with 3-phase true RMS AC sensing
- Multi-lingual capability: 10 languages
English, German, French, Italian, Spanish, Portugese, Russian, Turkish, Chinese, Japanese
- Flexible and multifunctional Dynamic LCD
- True rms sensing of voltage with FlexRange
- True rms sensing of current/power
- kWh/kvarh meter
- Counters for engine starts, operating hours, maintenance call
- Event recorder (300 entries, FIFO) with real-time clock
- 8 discrete inputs / 11 discrete outputs
- 2 freely configurable analog inputs
- PC and/or front panel configurable
Communication:
- J1939 for ECU communication
- CANopen for external terminals (e.g. the IKD 1 extension card with up to 16 additional external I/Os)
- Woodward CAL protocol for configuration via PC and for the GW 4 gateway interface converter to communicate with PLCs
- Serial interfaces for configuration and interfacing with an external modem
Protection (generator/engine):
- Battery voltage
- Overspeed (ANSI# 12)
- Over/undervoltage (ANSI# 59/27)
- Over/underfrequency (ANSI# 81O/U)
- Overload (ANSI# 32)
- Reverse/reduced power (ANSI# 32R/F)
- Unbalanced load (ANSI# 46)
- Definite time-overcurrent (ANSI# 50/51)
- Inverse time-overcurrent (IEC 255)
- Calculated/measured ground fault
Typical application:

Certifications / registrations: UL/cUL, CE, GL, LR
Download Product Specs:
Download Product Manuals:
Download Application Notes:
Download Brief Operation Information Sheet:
Download LeoPC1 Configuration Files:
Download LeoPC1 Configuration Program
Download GetEventLog Software
Please refer to the
Woodward Worldwide Directory and contact your
local sales office for questions about pricing and delivery or product support.
Return to top of the page
Note: Information contained herein is intended for and appropriate to
the purposes of this publication. Woodward reserves the right to update or otherwise
revise any portion of this publication at any time. Technical data and detailed
information is available in Woodward product specs. Specific reliance should be given
only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate
for the specific facts, circumstances and applications.
|