The easYgen-320 offers automatic engine starting, stopping, metering, and generator protection (the easYgen-350 adds AMF
(Auto Mains Failure) and transfer switch operations). The easYgen-300 series is designed for single unit isolated operation applications.
The multi-purpose 6-digit, 7-segment LED offers the ability to display measured values and alarm messages. The CAN bus operation adds the
ability to display J1939 messages from an engine ECU.
The Isolated J1939 CAN bus permits ECU connectivity. Our sales department
can provide information regarding the selected ECU manufacturers.
- Start/stop sequence for Diesel engines
- Pre-glow control
- Operating hours, service hours, and start counters
- Configurable thresholds, delays, alarm classes
- 6-digit 7-segment LED display for
- Measuring values (voltage, frequency, speed)
- Counters (operating/service hours, starts)
- Alarms
- ECU messages
- PC and front panel configurable
- 15 entry event logger
- Customized display using paper-strips
- Battery voltage
- Overspeed (ANSI# 12)
- Over/undervoltage (ANSI# 59/27)
- Over/underfrequency (ANSI# 81O/U)
- Charge alternator failure
- J1939 amber warning lamp
- J1939 red stop lamp
Models: easYgen-320 easYgen-320/X
- Generator circuit breaker (GCB) operation
- 1-phase generator true RMS voltage measuring (rated 480 Vac)
- Max. 2 configurable discrete inputs
- 1 freely porgrammable relay output

Return to top of the page
Models: easYgen-350 easYgen-350/X
- Generator and mains circuit breaker (GCB & MCB) operation
- Additional 3-phase mains true RMS voltage measuring (rated 480 Vac)
- Max. 2 configurable discrete inputs
- 2 freely porgrammable relay outputs

Models: easYgen-320/X easYgen-350/X
Certifications / registrations: UL/cUL, CE
Download Product Specs:
Download Product Manual:
Download LeoPC1 Configuration Files:
Download LeoPC1 Configuration Program
Download GetEventLog Software
Download Paper Strips
Please refer to the
Woodward Worldwide Directory and contact your
local sales office for questions about pricing and delivery or product support.
Return to top of the page
Note: Information contained herein is intended for and appropriate to
the purposes of this publication. Woodward reserves the right to update or otherwise
revise any portion of this publication at any time. Technical data and detailed
information is available in Woodward product specs. Specific reliance should be given
only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate
for the specific facts, circumstances and applications.
|