GCP-32 (AMG 2/N2PB)

Genset control for Multiple/Parallel Operation

The GCP-30 Series genset control is designed to provide total control for multiple, medium to large sized applications. A network of the compact, versatile GCP-30 controls is capable of controlling up to 14 gensets with automatic sequencing. Load management features include automatic base loading/peak shaving, import/export control and emergency power/back up power generation.

The GCP-32 has logic for two circuit breakers including open/closed transition.

View GCP-32 single genset application
View GCP-32 multiple genset application

Common Product Features:

  • Synchronization
  • Isolated single-unit operation
  • Stand-by operation
  • Peak load operation (auto start / stop)
  • Mains parallel operation
  • Start/stop logic for Diesel/gas engines
  • Operating hours / start / maintenance / kWh counter
  • Configuration via PC or front panel
  • Language Manager
  • Discrete raise/lower controller for n (speed) / f (frequency) / P (real power)
  • Discrete raise/lower controller for V (voltage) / Q (reactive power)
  • Mains import / export power control
  • Load-dependent start / stop
  • Load / var sharing for up to 14 generators
  • MPU input
  • 16 configurable discrete alarm inputs
  • 7 configurable relay outputs
  • CAN bus communication for control of unit and remote monitoring
  • CE marked
  • UL/cUL listed
  • AMF operation
  • Open transition (break-before-make)
  • Closed transition (make-before-break)
  • Softloading

Protection Functions:

  • 3/4-wire measurement
  • Mains/generator over/undervoltage (ANSI# 59/27)
  • Mains/generator over/underfrequency (ANSI# 81O/U)
  • Mains phase/vector shift (ANSI# 78)
  • Generator overload (ANSI# 32)
  • Generator reverse/reduced power (ANSI# 32R/F)
  • Generator unbalanced load (ANSI# 46)
  • Generator time-overcurrent (TOC) (ANSI# 50)

Special X-Package Features:

Models:
GCP-32/XPD
GCP-32/XPQ
GCP-32/XPQ+SB03
GCP-32/XPQ+SC10

  • Real-time clock
  • Event recorder (50 entries)
  • Mains import / export power control via 20 mA
  • Active power set point via 0/4 to 20 mA
  • 7 configurable analog inputs
  • 2 configurable analog outputs
  • External operation mode selection via DI

Special Q-Package Features:

Models:
GCP-32/BPQ
GCP-32/XPQ
GCP-32/XPQ+SB03
GCP-32/XPQ+SC10

  • Analog raise / lower controller for n (speed) / f (frequency) / P (real power)
  • Analog raise / lower controller for V (voltage) / Q (reactive power)
  • PWM raise / lower controller for n (speed) / f (frequency) / P (real power)

Option SB03 Features:

Models:
GCP-32/XPQ+SB03

  • Serial communication with Caterpillar CCM (ECM & EMCP II)

Option SC10 Features:

Models:
GCP-32/XPQ+SC10

  • CAN bus communication with IKD 1, ST 3 and engine ECU (SAE J1939, Volvo EMS2, Scania S6, Deutz EMR, mtu ADEC, mtu MDEC)

Certifications / registrations: UL/cUL, CE

Download Product Specs:
English German Japanese Russian Turkish Chinese

Download Product Manuals:
English Installation German Installation
English Configuration German Configuration
English Operation German Operation Spanish Operation
English Application German Application
English Option SB German Option SB
English Option SC09/SC10 German Option SC09/SC10

Download Application Notes:
Using the proconX MGATE Ethernet Communication Gateway

Download LeoPC1 Configuration Files:
GCP-3215B/BPQ (P/N 8440-1613) GCP-3245B/BPQ (P/N 8440-1614)
GCP-3215B/XPD (P/N 8440-1570) GCP-3245B/XPD (P/N 8440-1571)
GCP-3215B/XPQ (P/N 8440-1574) GCP-3245B/XPQ (P/N 8440-1575)
GCP-3215B/XPQ+SB03 (P/N 8440-1578) GCP-3245B/XPQ+SB03 (P/N 8440-1579)
GCP-3215B/XPQ+SC10 (P/N 8440-1576) GCP-3245B/XPQ+SC10 (P/N 8440-1577)
Refer to the configuration files download page for other P/Ns

Download LeoPC1 Configuration Program

Please refer to the Woodward Worldwide Directory and contact your local sales office for questions about pricing and delivery or product support.

Return to top of the page

Note: Information contained herein is intended for and appropriate to the purposes of this publication. Woodward reserves the right to update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances and applications.

Woodward Home | Search | SiteMap | Contact and Support | Copyright and Terms of Use