The SYNCONpanel is a remote synchronizing panel that transfers a local measured
delta between two voltage systems via CAN bus to the genset control GCP-31/RPQ+SC08.
For maintenance on a high voltage transformer or on the high voltage utility it is necessary
to supply the load of the isolated (and with switching the transformer OFF) voltage free busbar
with power. Therefore one or several mobile container(s) with gensets can be used. Because this
containers are placed outside the building with the transformer the service personnel needs an
direct access to remote set the frequency and the voltage of the mobile genset for synchronization.
If there is no circuit breaker but only a fuse accessible a need for the additional feature
"zero-angle-control" at that point is necessary.
The user locally measures voltage V(L1-N) of the one
system and voltage V(L1-N) of the other system via
direct measuring inputs on the front of the SYNCONpanel. In the SYNCONpanel
package is the control unit SYNCON included which compares those two voltages
with each other. A delta angle and delta voltage value are calculated
and displayed in the LC display. This value is transferred via a CAN bus
to the genset control GCP-31/RPQ+SC08 which is situated in the mobile
genset container. There the control of frequency and voltage are progressed.
View typical SYNCONpanel application
- True RMS voltage (A and B side)
- True RMS current (A side)
- Synch-check functionality
- Remote control of frequency, voltage, real power, and power factor
- Zero-phase-angle-control
- Zero power transfer control (softload)
- Two-line LC display
- CAN bus communication
Certifications / registrations: CE
Download Product Specs:
Download Product Manuals:
Please refer to the
Woodward Worldwide Directory and contact your
local sales office for questions about pricing and delivery or product support.
Return to top of the page
Note: Information contained herein is intended for and appropriate to
the purposes of this publication. Woodward reserves the right to update or otherwise
revise any portion of this publication at any time. Technical data and detailed
information is available in Woodward product specs. Specific reliance should be given
only to information contained in purchase order(s), other contractual document(s), or
information otherwise expressly represented in writing by Woodward as correct and accurate
for the specific facts, circumstances and applications.
|