SPM-D11 Series

Woodward Comprehensive Synchronizer And Load Share Unit

device_spm-d11.jpg 

The SPM-D11 Series are microprocessor-based synchronizers designed for use on one- or three-phase AC generators equipped with Woodward or other compatible speed controls and automatic voltage regulators. The SPM-D11 Series synchronizers provide automatic frequency, phase, and voltage matching, using either analog or discrete output bias signals. It combines synchronizing for one circuit breaker, load and power factor control, or isochronous load sharing and generator protection.

Features include: 

  • Synchronization for one circuit breaker
  • Phase match or slip frequency synchronization with voltage matching
  • Outputs for speed and voltage bias signals
  • Active power and power factor control
  • Two analog load share lines for active and re-active power load sharing
  • Analog input to control active power set point externally
  • Generator protection included
  • Discrete inputs for operating mode selection
  • Two-line liquid crystal text display for operation, alarm indication, and visualization of measuring values
  • LED synchronoscope
  • PC and front panel configurable
 

Packages

The SPM-D11 Series is available with different feature packages. The following table shows the differences between these packages.

 

 

SPM-D11 Series

Model 

SPM-D11 

(12/24 Vdc) 

SPM-D11 

SPM-D11 

(12/24 Vdc) 

SPM-D11 

Package

LSR (12/24 Vdc)

LSXR (12/24 Vdc)

LSR (24 Vdc)

LSXR (24 Vdc)

Three step controller
(voltage bias)

1

1

1

1

Three step controller
(speed bias)

1

1

1

1

Analog controller
(voltage bias)

---

1

---

1

Analog controller
(speed bias)

---

1

---

1

Power supply

12/24 Vdc

12/24 Vdc

24 Vdc

24 Vdc

Discrete input rating

12/24 Vdc

12/24 Vdc

18 to 250 Vac/dc

18 to 250 Vac/dc


 

Specifications

Power supply 

12/24 Vdc (9.5 to 32 Vdc) / 24 Vdc (18 to 32 Vdc)
(depeding on package)

Consumption

max. 10W

Ambient temperature

-20 to 70 °C

Ambient humidity

95 %, non-condensing

Voltage AC input 

115Vac or 400Vac true RMS

Accuracy

Class 1

Current AC input 

1A or 5A true RMS

Accuracy Iac

Class 1

Discrete inputs (isolated)

Range: 12/24Vdc or 18 to 250 Vac/dc

Relay outputs 

Isolated

Load (resistive)

2A@24Vdc and 250Vac

Housing 

 

Front panel mounting

Plastic housing

Dimension (WxHxD)

144 × 72 × 122 mm

Sealing (front/back)

IP42/IP21

Weight 

Approx. 800 g


 

Applications

application_spm-d11.gif

Approvals

CE.gif UL.gif cUL.gif GOST-R.gif 


 


 