CLOSE
Zoom
Zoom
Zoom
Zoom
Zoom
* Image may not reflect selected features
8237-1493

ProTech-MSM

HV/HV, IR, VI

The MicroNetâ„¢ Safety Module is a safety PLC with integrated overspeed and over-acceleration protection designed to safely shut down any steam, gas, or hydro turbine upon sensing a safety event. Available with two dual-redundant trip relay outputs using 2-out-of-3 voted architecture, or with three independent non-voted trip relay outputs. The MicroNet Safety Module is designed to be applied as part of a MicroNet control system. This ProTech MSM model is a bulkhead mount, high voltage/high voltage power input, independent relays/voted inputs safety device for steam turbine overspeed protection.
Product Type
  • Application Notes
  • Brochure
  • Product Specification
  • Software Manual
  • Technical Manual
  • Software
FEATURES & FUNCTIONALITY

High Resolution Displays

  • Each module includes a high resolution 4.2” (107 mm) color display and keypad to allow users to locally monitor configuration settings, statuses, system inputs and outputs, and alarm, trip, and overspeed logs.

Automatic Overspeed Test Routine

  • Optionally, the MSM can be configured to routinely perform and overspeed test each module/trip solenoid, then log and report the test results. With this test routine, each module is sequenced through its test sequence using an internal frequency generator to emulate an overspeed condition.

Automatic Test Routines

  • Optionally, the MSM can be configured to routinely perform custom tests of each module/trip solenoid, then log and report the test results. With this test routine, each module is sequenced through a programmed test sequence to simulate, test, and log the results of each safety even condition.

Acceleration/Deceleration Detection

  • Optionally, the MSM can be configured to protect a turbine from high acceleration/deceleration events. The derivative of the speed signal is used to detect turbine acceleration/deceleration and issue an associated trip command.

MPU Detection

  • Each module’s speed sensor input uses special MPU open-wire detection circuitry to validate that the MPU is properly connected before turbine operation, and special loss-of-speed detection logic to validate MPU functionality during turbine operation.

Sulfur Contamination Resistant

  • Utilizes special conformal coating material that has demonstrated excellent long-term protection against H2S and SO2 gases at levels classified in international standard IEC 721-3-3 1994 - environment Class 3C2 

Download

Brochure
Name
Item Number
Language
PROTECTING YOUR ASSETS--SAFETY SYSTEMS FOR TURBINES AND COMPRESSORS
51483
English
Product Specification
Name
Item Number
Language
MICRONET SAFETY MODULE
03375
English
Technical Manual
Name
Item Number
Language
MICRONET SAFETY MODULE FAULT TOLERANT PROTECTION SYSTEM W/ VOTED INPUTS (VOL. 1)
26711V1
English